PD18 |
Fill Timeout Value |
PD18 |
Command Group: Filling | Access: | Network interfaces: | ||
RW | CANopen | SDO2200sub12 | ||
MODbus | 2322,2 | |||
PD18 - Terminate filling cycle after timeout. | PROFIbus | read 6,18 write 6,146 |
|
|
PD18 The LDM subtracts the various delays and average times (P3..P9) from the timeout period ‘PD18’ and uses the ‘remaining’ fill time and Fill-weight to calculate a minimum filling slope. If the weight doesn’t stay between this minimum slope and twice the minimum slope the LDM aborts the filling cycle and reports a filling failure. The Filling cycle will also be aborted if the timeout value P18 expires.
If P18 = 0, the timeout is disabled.