H3

hyst. sp 3

H3


Command Group: Setpoints

Access:

Network interfaces:

RW

CANopen

SDO2700sub04

MODbus

206A,2 select 2067,1,3

H0 - Set the hysteresis value for setpoint 3

PROFIbus

read 29,$23 write 29,$53


Synopsis:
CommandResponse
GetH3H3:<Value>
SetH3 <Value>OK (or ERR)
Valid forMin. valueMax. value
151.181 -32768 32767
152.181 -32768 32767
64.181 -9999 9999
72.181 -99999 99999
88.183 -262143 262143



H3 Set the hysteresis value for channel 3. sets the value and polarity by which the output value must change in order to assert or release the setpoint output.
Issuing the H3 command without any parameters will return the current value in the form H3:+00100. , signifying that the setpoint must hold it’s “ON” status until the source value drops below S3-100.
If H1 is set to a negative value, then this signifies that the source value must increase beyond S3+100, after which point the setpoint will release, and the relevant output channel will change to the “OFF” condition. This command therefore allows the setpoint to be inverted.

See also A0, A1, A2, A3, S0, S1, S2, S3, H0, H1, H2, P1, P2, P3.