H2

hyst. sp 2

H2


Command Group: Setpoints

Access:

Network interfaces:

RW

CANopen

SDO2700sub03

MODbus

206A,2 select 2067,1,2

H0 - Set the hysteresis value for setpoint 2

PROFIbus

read 29,$22 write 29,$52


Synopsis:
CommandResponse
GetH2H2:<Value>
SetH2 <Value>OK (or ERR)
Valid forMin. valueMax. value
141.181 -32768 32767
141.184 -32768 32767
141.185 -32768 32767
142.181 -32768 32767
142.184 -32768 32767
142.185 -32768 32767
142.186 -32768 32767
143.181 -32768 32767
143.184 -32768 32767
143.185 -32768 32767
151.181 -32768 32767
151.184 -32768 32767
151.186 -32768 32767
152.181 -32768 32767
152.184 -32768 32767
64.181 -9999 9999
72.181 -99999 99999
88.183 -262143 262143



H2 Set the hysteresis value for channel 2. sets the value and polarity by which the output value must change in order to assert or release the setpoint output.
Issuing the H2 command without any parameters will return the current value in the form H2:+00100. , signifying that the setpoint must hold it’s “ON” status until the source value drops below S2-100.
If H1 is set to a negative value, then this signifies that the source value must increase beyond S2+100, after which point the setpoint will release, and the relevant output channel will change to the “OFF” condition. This command therefore allows the setpoint to be inverted.

See also A0, A1, A2, A3, S0, S1, S2, S3, H0, H1, H3, P1, P2, P3.